Integration: HVAC fans and smoke control

05/20/2013


Ductwork 

Figure 4: A typical HVAC control system graphic panel allows the user to view system performance and make modifications as needed. Courtesy: Trane Co.There is no real difference between ductwork in the distribution system used for HVAC and smoke control systems. The only changes are that the ductwork is required to be supported by fire-resistance rated structural elements using noncombustible supports. There is no specific requirement as to the type of material to be used, other than what is required for HVAC systems. Ducts can be made from sheet metal or can be made of drywall. 

Duct materials and joints are required by the IBC to be capable of withstanding the probable temperatures and pressures to which they will be exposed. They are required to be leak tested to 1.5 times the maximum design pressure. The designer needs to document the design pressure of the duct, which is often different than the fan static pressure. The measured leakage cannot exceed 5% of the design flow. While not specifically outlined in the code, leak testing is typically done only for exhaust systems that traverse other smoke zones to confirm they will not leak significant amounts of smoke when exhausting the fire zone. Ducts that are contained only within the zone or supply air systems do not have the potential to convey smoke outside of the initial zone. Therefore, it is typical to see the designer identify those ducts requiring leak testing and not all ducts. It would be reasonable to expect vertical ducts traversing multiple floors to be leak tested, but not the portion of the duct that is isolated to the zone. 

Another issue that has been encountered in the use of HVAC systems for smoke control is the use of ducts made of drywall materials. Leakage rates for HVAC systems may not be impacted for climate control the same as they are for smoke control. Experience has shown that when using drywall ducts for smoke control systems, it is difficult at best to meet the leakage testing requirements. Often metal ductwork has had to be installed to replace the drywall ducts to meet the leak testing. Therefore, metal ductwork should be used wherever possible to prevent impact by leak testing during commissioning of the system. 

Additional considerations should be taken when determining the location of exhaust/return fan discharge outlets and their associated fans. Fans used for exhaust in a smoke control or smoke removal system should not discharge at locations where the potential exists for reintroducing smoke into the building or any adjacent buildings. 

Figure 5: This firefighter’s smoke control graphic panel shows controls, status indicators, and graphic configuration of system. Courtesy: HR KirklandControl systems 

Smoke control mode, as defined by NFPA 92, is a predefined operational configuration of a system or device for the purpose of smoke control. This is accomplished by a set of predefined sequences programmed into the smoke control system. The smoke control system can be either a subset of the building’s fire alarm system, or a combination of the building’s automation and fire alarm system. When HVAC systems are being used, some form of building automation system (BAS) is commonly part of the overall smoke control system. 

A smoke control system requires input from the field to determine when to configure the system. This is done primarily through the fire alarm system’s smoke detectors or monitoring of the building’s automatic sprinkler system. When the fire alarm system detects one of these conditions, a signal is processed and the smoke control system is configured for its predetermined sequence for that zone in the building. Depending upon the control system concept employed, either the fire alarm system drives all sequences overriding the BAS or a handoff of signals occurs allowing the BAS to control all or a portion of the system. In a typical high-rise building, it is usually a combination of the BAS and fire alarm system controlling equipment.

It is common to see both BAS and fire alarm systems control the overall smoke control system. While it is also common to see just the fire alarm system, this can duplicate controls and wiring and drive costs. If the BAS is suited for smoke control functions (in the United States, UUKL listed by UL for smoke control purposes), then it is acceptable to have both systems control fans and dampers appropriately. In high-rise office buildings where HVAC systems are used for both climate and smoke control, the fire alarm system can hand off a signal to the HVAC/BAS to configure dampers and fans already being controlled for climate control purposes. Other fans, such as stairwell pressurization fans, do not have HVAC controls and can be controlled directly by the fire alarm system. 

The designers of the smoke control and HVAC systems must collaborate to determine the most cost-effective and reliable source for controlling the system. If the designers are one and the same, consideration should be given to how to achieve the proper control functions using reliable equipment already in place. This not only applies to the field circuits and controls but also to graphic interface panels. It is not practical to have two separate graphic control panels for one overall smoke control system. When using two control systems, the user interface needs to be considered to allow for efficient control and overrides of the system in an emergency condition. 

Overall, it is common to see HVAC systems employed for smoke control purposes. It can save money and can provide for reliable operation. When considering the use of dual-purpose equipment, such as HVAC systems, take into account the impact the smoke control operation and code requirements have on HVAC functions and whether the HVAC system can function as intended for emergency conditions.


Allyn J. Vaughn is CTO/president at jba consulting engineers. He has been in Las Vegas for more than 15 years providing fire protection system design and code consulting services, including design and commissioning of smoke control systems. Stephen Haines is project engineer with jba consulting engineers. He has more than 5 years of experience designing HVAC systems for smoke control in various high-rise buildings in Nevada, Arizona, California, and Macau, China


<< First < Previous 1 2 3 Next > Last >>

No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
The true cost of lubrication: Three keys to consider when evaluating oils; Plant Engineering Lubrication Guide; 11 ways to protect bearing assets; Is lubrication part of your KPIs?
Contract maintenance: 5 ways to keep things humming while keeping an eye on costs; Pneumatic systems; Energy monitoring; The sixth 'S' is safety
Transport your data: Supply chain information critical to operational excellence; High-voltage faults; Portable cooling; Safety automation isn't automatic
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Maintaining low data center PUE; Using eco mode in UPS systems; Commissioning electrical and power systems; Exploring dc power distribution alternatives
Synchronizing industrial Ethernet networks; Selecting protocol conversion gateways; Integrating HMIs with PLCs and PACs
Why manufacturers need to see energy in a different light: Current approaches to energy management yield quick savings, but leave plant managers searching for ways of improving on those early gains.

Annual Salary Survey

Participate in the 2013 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.