VFDs: The path to prolonged life

Proper maintenance and attention to detail can stretch productivity

11/18/2013


Figure 1: This is an example of a motor bearing lubrication fitting. Courtesy: DanfossOne of the main factors for obtaining long reliable service from any piece of equipment is maintenance. Any type of electrical or mechanical device is subject to wear and tear. This can be further aggravated by undesirable environmental conditions.

Heat, moisture, dust, dirt, poor electrical connections, and poor ground connections can cause premature failures. They can also cause the normal service life of the equipment to be shortened considerably. A piece of equipment employing the use of a motor controlled by a Variable Frequency Drive is no exception.

Many manufacturers of motors and VFDs as well as companies specializing in the service of these products, offer service related products such as PM contracts to assist the user in maintaining the equipment.

Regardless of the type or brand of motor or VFD, there are some common areas that require attention during maintenance procedures. These can be categorized as electrical, mechanical, and environmental. Though these three areas can sometimes be quite interrelated, we will address them individually. 

Mechanical

As any mechanic will tell you, keeping all moving parts aligned and lubricated will yield the most reliability and longest service life out of any piece of equipment.

Improper alignment of belts or shafts will result in undo stress or vibration. Shaft and pulley alignment should be checked periodically. Also, the condition of belts should be checked at the same time. Excessive wear of belts can sometimes indicate alignment problems.

Of course, maintaining the proper lubrication of all bearings is necessary. Lack of lubrication, or in some cases over lubrication can result in excessive wear on the bearing. Another area of concern here is using the proper lubricant. Sometimes the decision as to which type of oil or grease to use depends on the purchase price of that substance. It is important to remember that the wrong type of grease can be just as damaging as no grease at all. One should always follow the equipment manufacturers’ specification as to the type of lubricant and frequency of application. 

Electrical

Figure 2: This is an example of a power terminal block on a VFD showing fastener torque on the label. Courtesy: DanfossProbably the most common function in the PM procedure for any piece of electrical equipment is to check that all electrical connections are tightened properly. Poor connections can cause a variety of problems ranging from instantaneous failure to excessive mechanical wear. All screw type electrical connections should be checked at least annually to ensure that they are tightened to the proper torque.

One mistake often made by maintenance personnel is to tighten the terminal screw as tight as possible. That is almost never correct. Every screw type electrical terminal has particular torque specification. Often these specified torque values will seem somewhat low for the size of the terminal screw. Many people will see a large terminal screw and instinctively want to tighten it with a great deal of torque. Remember, the size of the terminal screw has more to do with the amount of current in that circuit than the physical strength requirement. Over tightening these screws can cause deformation in the terminal or the wire resulting in a poor electrical connection. 

If there is a considerable amount of dirt, oil, or other contaminants in the surrounding area, the exposed areas of the connection may also require periodic cleaning as well. This is especially true if the surfaces in the connection are oxidized or corroded.

Ground connections are of particular concern in any electrical installation. This is especially true when a motor is being controlled by a VFD. In addition to the amount of potential noise interference created anytime an AC motor is connected to an electrical power source, there is also the switching frequency from the VFD along with some common mode voltages associated with using a VFD.

There are two main functions of a ground connection. One is to establish a ground level potential on the enclosure of a device to protect against electrical shock hazard for any personnel that may come in contact with the equipment. This is normally referred to as a low frequency ground.

The other function is to enable any structure or enclosure to act as a shield to prevent noise interference from entering or exiting the equipment. This is often referred to as a high frequency ground connection. With a high frequency ground, the integrity of the connection is much more critical. Ground connections should be checked and cleaned periodically to ensure that the high frequency capability of the connection is maintained. A good high frequency ground connection on the motor can reduce the damage caused by bearing currents induced by common mode voltages, and eddy currents from asymmetrical coil windings in the motor.

Environmental

There are several environmental factors that can affect the life and reliability of a motor/VFD system.

One of the major factors is, of course, temperature. This can be caused by weather of the location where the system is installed or by the heat that is being produced by the equipment itself.

Heat can be considered the common enemy of any type of equipment whether it is electrical or mechanical. VFDs typically have efficiency ratings that range from 92 – 98%. This means that for every kilowatt of electrical power that is being used, 20 – 80 watts are being dissipated in the form of heat.

By design, most manufacturers of motors and VFDs have included a method to remove excess heat. These normally consist of a cooling medium (either air or liquid) passing along a heat exchanger or heatsink. The operative word is passing. This means that in order for the cooling medium to do its job effectively it must be moving along or through the heat exchanger.

Figure 3: This is an example of a common air inset/outlet filter assembly for a NEMA 12 rated panel. Courtesy: DanfossA major maintenance function is to ensure that all cooling air or fluid passageways are free from clogs or obstruction that can reduce flow. Heatsinks and heat exchangers must be cleaned periodically to remove any dirt or material that would obstruct flow.

Quite often when the VFD is mounted in an enclosure with a NEMA type 12, 4 or 3R rating, an air filter is used to keep contaminants out. These filters must be cleaned or replaced periodically. The frequency depends upon the amount of dirt or contaminants present.

Of course, all fans and circulating pumps must be checked to ensure that they are in proper working order.

One major concern is cleanliness. While this has been alluded to a number of times in this article, it requires reiterating. Dust, dirt, and other contaminants can cause failures in every aspect of a motor/VFD system. Therefore a major function of anyone responsible for maintenance is cleaning of the equipment and surrounding area.

If the VFD or any other electrical equipment is mounted in a type 12, 4, 4X, or 3R enclosure, the cabinet door gaskets must also be checked to ensure that the integrity of the enclosure is maintained. It must also be emphasized that it is important to close and latch cabinet doors when work in that cabinet is complete. It is not uncommon to find 4X enclosures with the door held closed by only one insufficiently tightened door clamp. The rating of an enclosure is only valid when the door is closed and latched properly.

The lack of regular maintenance can result in premature failures of either VFDs or motors. The extra expense of a regularly scheduled preventative maintenance program is considerably low compared to the cost of repairs or replacement of motors or VFD’s.

The primary reason for the use of VFD’s is to increase efficiency in processes and power consumption, and to save money. Proper maintenance will ensure you are able to continue on that path during the life of the system. 

Gregory Finch is Service Training Manager for Danfoss VLT Drives.

Key Points:

  • There are common elements and strategies to the proper maintenance of VFDs
  • Align and lubricate all moving parts
  • Make sure electrical connections are properly tightened
  • Be sure to monitor such things as temperature and environment 

See more on VFDs below.



Bob , PA, United States, 12/05/13 10:13 AM:

Very well said, often field maintenance overlooks these important factors.Are torque specs for terminals usually in startup/installer manuals?
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Leaders Under 40 program features outstanding young people who are making a difference in manufacturing. View the 2013 Leaders here.
The new control room: It's got all the bells and whistles - and alarms, too; Remote maintenance; Specifying VFDs
2014 forecast issue: To serve and to manufacture - Veterans will bring skill and discipline to the plant floor if we can find a way to get them there.
2013 Top Plant: Lincoln Electric Company, Cleveland, Ohio
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Bring focus to PLC programming: 5 things to avoid in putting your system together; Managing the DCS upgrade; PLM upgrade: a step-by-step approach
Balancing the bagging triangle; PID tuning improves process efficiency; Standardizing control room HMIs
Commissioning electrical systems in mission critical facilities; Anticipating the Smart Grid; Mitigating arc flash hazards in medium-voltage switchgear; Comparing generator sizing software

Annual Salary Survey

Participate in the 2013 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.