Temperature diagnostics help prevent unplanned shutdowns

Your instrumentation may be trying to warn you of a developing problem. Usually this warning will give you time to prevent a production interruption, if you’re paying attention.

03/07/2014


In most industrial process plants, unit operations have become increasingly complex. That combined with the ever-increasing demands on operations and maintenance personnel for their time, make it very difficult for them to proactively monitor the health and performance of all measurement and control instrumentation. As a result, many problems go unnoticed until they cause production or quality issues, or even worse, an unscheduled shutdown.

In today's modern process plants, production and quality systems put new and much tighter requirements on the accuracy and performance of process instruments and control. Proactive identification of performance issues before production is impacted has become the rule and not the exception in many facilities. As a result, many plants have turned to diagnostics as a way to identify issues before they become problems. For example, the diagnostic features designed into temperature transmitters monitor the process and provide diagnostic information. As a result, issues are identified before they cause process upsets, dangerous conditions, or measurement failure.

Temperature transmitters have an enormous capability to run full-time diagnostics. Many offer a vast array of options and features to assure that an accurate and stable measurement is reported to the control system. Many of these alerts can prioritize maintenance scheduling for more efficient use of available maintenance resources.

Understanding temperature transmitters and diagnostics

While all smart temperature transmitters have diagnostics, some are considerably more extensive than others. There are normally internal diagnostics that monitor transmitter functionality and output validity. Also, there is a wide range of external diagnostic functions that monitor the measurement signal for drift, degradation, measurement validity, and broken or damaged leads. Of all transmitters that are available, those that use HART, Foundation fieldbus, or Profibus protocols offer a high level of sophistication.

Transmitters initiate either alerts or alarms based upon these diagnostic processes. Alerts cover diagnostics that are determined not to affect the transmitter's ability to output the correct measurement signal reflecting the process variable (PV) and therefore will not interrupt the 4-20 mA or digital fieldbus output. A typical example of an alert could be "PV out-of-range."

Alarms cover diagnostics that are determined to affect the transmitter's ability to output an accurate PV value of the measurement. Detected alarms will drive the transmitter output either high or low depending on the user's configuration choice. Alerts and alarms can be sent to the control system, read on a local indicator, on a field communicator, or on a HART-compliant monitoring system as seen in Figure 1.

Accessing diagnostic information

Alerts and alarms can be sent to the control system, read on a local indicator, on a field communicator, or on a HART-compliant monitoring system. Courtesy: Emerson Process ManagementAt a basic level, transmitters with display options will present certain diagnostic messages. Typically, the field operator will routinely check these displays and report any diagnostic conditions to the control system technician group.

The most frequently deployed transmitters communicate using 4-20 mA with HART. This allows them to send a large amount of operational and diagnostic data via the HART signal that is superimposed on the analog output signal of the transmitter. Any or all of this data may be accessed via:

  • A hand-held field communicator
  • A HART-enabled capability in the DCS I/O systems to extract and monitor the HART data, and
  • A HART-enabled asset management system.

As with traditional wired HART transmitters described above, that same information can be sent using a WirelessHART transmitter or one using ISA100.11a. For Foundation fieldbus and Profibus systems, the operational and diagnostic information available is also very extensive.

The operations-maintenance relationship

Close coordination between operators and technicians to review diagnostic information routinely enables quick identification and resolution of problem situations before they can adversely impact production. One example is in relation to a dual sensor redundant measurement. If an operator gets a diagnostic message that the secondary sensor has been initiated for a transmitter, he or she knows that the primary sensor has failed and that the measurement is now coming from the secondary sensor. By alerting the maintenance technician, the failed sensor can be replaced, thus restoring the measurement redundancy capability.

Another example is regarding when the PV is out of limits. An operator receives a "PV out of limits" alert where the HART transmitter is reporting that the primary variable read by the transmitter is outside of the 4-20 mA range. This signal could focus the technician on troubleshooting open or short circuits in the transmitter wiring. Yet another example is regarding analog-digital mismatch. The HART transmitter is reporting a difference between the analog 4-20 mA signal and the digital primary PV signal. This functionality can be used to determine a small ground leakage in the home-run cable to the instrument or an intermittent device. If a small ground leakage exists in the loop, any alarm trip limit of the loop may never be reached, even under trip conditions, due to earth leakage from the signal.

Avoiding the biggest issues

The three biggest issues that diagnostics help you to avoid are measurement failure, poor measurement reliability, and suboptimal process control.

Measurement failure occurs when any of the components of the overall temperature system fail. Temperature sensors are relatively delicate and are exposed to the harsh process environment, making them more susceptible to failure than the other components. The use of redundancy, drift detection, and monitoring of the measurement instrument's diagnostics all help to identify and address sensor degradation or failure.

Many benefits can be gained by using diagnostics in a manufacturing process. Courtesy: Emerson Process ManagementMeasurement reliability is key to minimizing disruptions to the process. The temperature measurement system should be designed to minimize or eliminate the problems caused by sensor degradation, electrically noisy environments, or instrument failure to ensure a reliable measurement. The design should use such features as noise filtering, measurement validation, drifting sensor identification, and alerts for broken or loose sensor leads.

The ultimate goal of providing an accurate and reliable measurement signal is to ensure process control reliably keeps the process within its predetermined limits. The diligent use of transmitter diagnostic features can identify situations where these limits are violated and identify and quantify the deviations. They can identify intermittent sensor failures, record minimum and maximum process temperatures, and log failures and their causes. Using this information can support rapid response to address identified issues, so as to ensure optimal process control is maintained.

Each approach has its own benefits

Many benefits can be gained by using diagnostics in a manufacturing process. A few have been outlined in Chart 1. For example, measurement failure is related to sensor failure. As mentioned earlier, sensors are relatively delicate, but for the sake of getting the most accurate readings, they must be exposed to the often harsh process environment, making them more susceptible to failure than the other components. Without an accurate and reliable measurement signal, control will be sub-optimal and the system will be unable to keep the process within predetermined limits.

The bottom line

Judicious use of the diagnostics available in almost every temperature measurement system provides a return on this investment (ROI) in proportion to the criticality of the measurement. The investment is mostly in time spent, and the ROI may be measured in increased throughput, higher product quality, less downtime, less product waste, lower energy costs, or more subjectively, prevention of an explosion.

Your instrumentation provides the means to look into the process. Using diagnostics provides a way to keep that window clean.

Michelle Weimert is a senior manager, temperature marketing and product development, for Emerson Process Management.

Key concepts:

  • Diagnostic information from smart transmitters can warn of problems developing with a process sensor.
  • The physical delicacy of temperature sensors makes them particularly susceptible to damage or degradation.
  • Your ability to control a process depends on the accuracy and reliability of your instrumentation. Diagnostics help ensure that reliability.

ONLINE 

This is the fifth part of this temperature series. Read the earlier installments below.

To learn more about measuring temperature in process manufacturing applications, go to www.rosemount.com/tempguide and order a free copy of The Engineer's Guide to Industrial Temperature Measurement.

www.emersonprocess.com 

Subscribe to the Process Instrumentation & Sensors Monthly eNewsletter 



No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
The true cost of lubrication: Three keys to consider when evaluating oils; Plant Engineering Lubrication Guide; 11 ways to protect bearing assets; Is lubrication part of your KPIs?
Contract maintenance: 5 ways to keep things humming while keeping an eye on costs; Pneumatic systems; Energy monitoring; The sixth 'S' is safety
Transport your data: Supply chain information critical to operational excellence; High-voltage faults; Portable cooling; Safety automation isn't automatic
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Maintaining low data center PUE; Using eco mode in UPS systems; Commissioning electrical and power systems; Exploring dc power distribution alternatives
Synchronizing industrial Ethernet networks; Selecting protocol conversion gateways; Integrating HMIs with PLCs and PACs
Why manufacturers need to see energy in a different light: Current approaches to energy management yield quick savings, but leave plant managers searching for ways of improving on those early gains.

Annual Salary Survey

Participate in the 2013 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.