Selecting chillers, chilled water systems

09/16/2013


Chilled water pumping arrangements

A chiller plant is not complete without the pumping arrangement to distribute chilled water throughout the building or campus to the chilled water coils. There are multiple arrangements for distributing chilled water. This article will describe the two most commonly used methods of chilled water pumping, variable primary flow (VPF) and primary-secondary, and how they relate to initial investment costs and operating costs for the chiller plant. 

In both pumping schemes, the flow to chilled water coils in the system is variable flow as the cooling coils are equipped with two-way temperature control valves. The difference exists in the way the pumping is handled through the chillers. In a VPF system, the flow varies in the entire system, including through the chillers, which is a shift from the previous mind-set that chillers always require a constant flow through the evaporator. However, recent advances in control technology have allowed the ability to vary the flow through the evaporators within the manufacturer’s recommended ranges and can provide substantial energy savings. 

Because of the ability to vary flow, these systems eliminate the need for secondary distribution pumps and use multiple pumps in parallel to serve the entire chilled water system, including the chillers and any coils in the system. These pumps handle the entire system head at the required system flow rate. VPF requires a minimum flow bypass pipe, which includes a control valve to protect the chiller from falling below the minimum flow rate and temperature control isolation valves at each chiller to isolate flow through the chillers when they are not in operation. Some designers prefer three-way valves at a select number of coils to provide minimum system flow, but this will increase the pumping energy required in the system by increasing flow in all conditions except when the system is at minimum flow. The system minimum flow is maintained by using a flow meter or measuring the pressure drop across the chillers to determine system flow to control the bypass valve.

In a primary-secondary system, two sets of pumps are used, each with a dedicated function to the chilled water system. The primary pumps serve as production pumps and serve only the chillers in the system. These pumps are typically high-flow, low-head constant-flow pumps staged on with a chiller to provide available chilled water to the secondary pumps. The secondary pumps serve only the chilled water coils in the system, which are equipped with two-way control valves as explained above and are high-flow, high-head variable speed pumps that vary the system flow in response to the load. The primary and secondary loops are connected via a common pipe or decoupler that is a shared portion of the piping circuit in each loop that hydraulically separates the two loops so flow in one loop does not affect the flow in the other. This will allow the water to flow through the common pipe in either direction to hydraulically balance the system. These systems are typically older systems that require a constant flow through the chiller, but can still be used as a fail-safe solution due to their simplicity.

The advantages of VPF systems are directly related to the pumping concepts described above. VPF systems will always have fewer pumps compared to a primary-secondary system, which will save initial costs from less piping and valves, fewer electrical connections, less controls work, and no vibration isolation at the additional pumps.  Similarly, one set of pumps will save on mechanical room space requirements, which can lead to substantial initial cost savings in building footprint or increasing useable building square footage. The one thing that must be addressed is the more complex staging controls and ensuring minimum flow in the system at all times, but this will still maintain an overall net savings in initial cost. 

For operating costs, VPF systems will always have lower operating costs as there is less pressure drop in the system due to fewer pumps and accessories at the pumps, but also because the pumps will be more efficient. The VPF pumps allow the designer to select larger, more efficient horsepower pumps instead of smaller, constant volume, low efficiency circulator pumps typically found on the primary side of the primary-secondary system. Also, the use of variable speed in the entire system will allow the entire system flow rate to vary, which will provide operating cost savings as energy will vary approximately with the cubed power of the flow rate. This is in contrast to constant volume pumping and energy consumption at the primary pumps and variable flow at the secondary pumps in a typical primary-secondary system.

Chilled water plants and chillers are dynamic systems that rely on careful analysis to determine the right chiller for a building. There is no simple answer based on the type or size of the building; however, understanding the options based on building load and the compression methods can help narrow down the alternatives for further evaluation. One can select chiller variations that can be analyzed based on initial cost and overall system operating costs. A chiller with a more expensive initial investment may prove to have the best overall operating costs by using an energy simulation program that can evaluate the building load profile over time with respect to corresponding weather data. Clearly, there are multiple different chiller options, and careful analysis, rather than a blended kW/ton value, is required to make the best selection for your situation. 


David Grassl is a mechanical engineer at Ring & DuChateau, and an adjunct professor in the Civil & Architectural Engineering & Construction Management Department at the Milwaukee School of Engineering. He has analyzed and designed approximately 10,000 tons of chilled water systems for plants ranging from small, individual systems for office buildings to large, complex central plants for universities.


References

  1. Bhatia, A. 2012. Overview of Chiller Compressors. PDHengineer Course HV-4004. Houston, TX: PDHengineer.
  2. ASHRAE. 2011. Handbook of HVAC Applications. Atlanta, GA: American Society of Heating Refrigeration and Air Conditioning Engineers, Inc.
  3. AHRI. 2003. AHRI 550/590, Standard for Performance Rating of Water-Chilling Packages Using the Vapor Compression Cycle. Arlington, VA: Air Conditioning, Heating, and Refrigeration Institute.
  4. Geister, W. Ryan and Thompson, Mike. 2009. A Closer Look At Chiller Ratings. ASHRAE Journal, Vol. 51, No. 12, p. 22-32. Atlanta, GA: American Society of Heating, Refrigeration, and Air-Conditioning Engineers Inc.
  5. Taylor, Steven T. 2002. Primary-Only vs. Primary Secondary Variable Flow Systems. ASHRAE Journal, Vol. 44, No. 2, p. 25-29. Atlanta, GA: American Society of Heating, Refrigeration, and Air-Conditioning Engineers Inc.

 


<< First < Previous 1 2 3 4 Next > Last >>

No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
The true cost of lubrication: Three keys to consider when evaluating oils; Plant Engineering Lubrication Guide; 11 ways to protect bearing assets; Is lubrication part of your KPIs?
Contract maintenance: 5 ways to keep things humming while keeping an eye on costs; Pneumatic systems; Energy monitoring; The sixth 'S' is safety
Transport your data: Supply chain information critical to operational excellence; High-voltage faults; Portable cooling; Safety automation isn't automatic
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Maintaining low data center PUE; Using eco mode in UPS systems; Commissioning electrical and power systems; Exploring dc power distribution alternatives
Synchronizing industrial Ethernet networks; Selecting protocol conversion gateways; Integrating HMIs with PLCs and PACs
Why manufacturers need to see energy in a different light: Current approaches to energy management yield quick savings, but leave plant managers searching for ways of improving on those early gains.

Annual Salary Survey

Participate in the 2013 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.