NFPA 20: More key factors to consider

Other issues you should be aware of with the additions to the 2013 edition of NFPA 20.

06/25/2013


Figure 6: Incorrect elbow orientation in a pump suction is shown. Courtesy: Aon Fire Protection EngineeringDouble-wall fuel tanks: Language to clarify that a dike is not required for double-wall diesel oil fuel tanks for fire pumps was added to the 2013 edition of NFPA 20. It should be noted that NFPA 20 does not refer to NFPA 30: Flammable and Combustible Liquids Code, and therefore the requirement in NFPA 30 that requires all pipe into a double-wall fuel tank to be through the top of the tank does not apply to NFPA 20. NFPA 20 requires the diesel fuel line near the bottom of the tank to provide gravity feed to the diesel engine.

Elbows, tees in pump suction piping: While the requirement that the distance between the flanges of the pump suction intake and an elbow or tee must be greater than 10 times the suction pipe for elbows and tees that have a centerline plane parallel to a horizontal split-case pump shaft was not changed, the figures in the appendix demonstrating proper installation were clarified. See Figure 6 for an example of an elbow incorrectly installed with a centerline plane parallel to the horizontal split-case pump shaft.

Equipment access: Fire pump rooms that are not directly accessible from the outside must be accessible through an enclosed passageway from an enclosed stairway or exterior exit having a fire-resistance rating not less than the fire-resistance rating of the fire pump room.

Reliability measurement: The ongoing debate over what makes a “reliable” electrical source for fire pumps was not resolved and will continue to be studied for the next cycle. 


Gayle Pennel is a project manager with Aon Fire Protection Engineering. His expertise lies in fire protection systems and water supplies. He is currently chairman of the NFPA 20 committee and serves on the NFPA 25 committee. He has designed fire protection systems for super high-rise and large exhibition centers, as well as industrial sites. Pennel has consulted on pressure surge, corrosion, and other fire protection failure issues and has successfully presented fire protection design alternatives to state and local authorities.



No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Leaders Under 40 program features outstanding young people who are making a difference in manufacturing. View the 2013 Leaders here.
The new control room: It's got all the bells and whistles - and alarms, too; Remote maintenance; Specifying VFDs
2014 forecast issue: To serve and to manufacture - Veterans will bring skill and discipline to the plant floor if we can find a way to get them there.
2013 Top Plant: Lincoln Electric Company, Cleveland, Ohio
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Bring focus to PLC programming: 5 things to avoid in putting your system together; Managing the DCS upgrade; PLM upgrade: a step-by-step approach
Balancing the bagging triangle; PID tuning improves process efficiency; Standardizing control room HMIs
Commissioning electrical systems in mission critical facilities; Anticipating the Smart Grid; Mitigating arc flash hazards in medium-voltage switchgear; Comparing generator sizing software

Annual Salary Survey

Participate in the 2013 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.