Debunking the myths around arc flash safety, prevention

Steps on how to prevent arc flash and arc blast hazards and dispelling some popular myths about how they occur


According to the Electrical Safety Foundation, Int'l, 2,000 workers each year are admitted to burn centers for treatment of severe arc flash burns. While the threat of shock and electrocution from inadvertent contact with energized parts has long been recognized, arc flash and arc blast hazards have only recently been incorporated into the electrical safety standards.

This may be why the myth exists that arc flash incidents are rare. The National Fire Protection Association (NFPA) 70E: Standard for Electrical Safety in the Workplace is the document most often referenced for electrical safety, including arc flash safety. OSHA enforces electrical workplace safety standards outlined in NFPA 70E. Enforcement may take place following an electrical accident or during the agency’s normal on-site inspection process.

Companies that have not met the requirements of NFPA 70E should immediately take steps to begin the compliance process not only for worker safety, but also for equipment productivity. An arc flash accident can render equipment unusable and place the facility in a costly downtime mode, which could last hours or days.

Here are some of the other myths around arc flash safety and prevention:

Myth: Having an arc flash analysis performed deems a company’s workplace NFPA 70E compliant.

Basic compliance with the 2012 edition of NFPA 70E is actually established with a five-step process, which includes an arc flash analysis. The five steps are:

  1. Develop and audit on a regularly scheduled basis an electrical safe work practice policy.
  2. Conduct an electrical system study to determine the present degree of arc flash hazards and apply associated equipment labeling.
  3. Ensure adequate supplies of personal protective equipment (PPE) and proper tools for electrical workers.
  4. Conduct regularly scheduled safety training and audits for all electrical workers.
  5. Maintain all electrical distribution system equipment and components per manufacturers’ recommendations.  

Myth: There is no difference between the NFPA 70E Hazard/Risk Category Tables and the IEEE 1584 method for calculating arc energy levels to determine appropriate levels of PPE.

NFPA 70E provides Hazard/Risk Category tables, which highlight specific personal protective equipment to be used on various electrical distribution equipment. However, these tables are based on fundamental assumptions about the available fault current and the overcurrent device clearing time. In order to use the tables, the person in charge must verify that the available fault current and the overcurrent protective device (OCPD) tripping time are both equal to or lower than the values assumed for developing the tables.

The simplistic approach of selecting the arc flash hazard category based on equipment type, voltage, and the task being performed could subject the electrical workers to either too little PPE (risk of injury) or too much PPE (risk of reduced mobility). Therefore, in order to properly apply the tables, some degree of electrical calculations must be performed to calculate the fault current and to establish the overcurrent protective device tripping time. The tables could be subjected to misuse if they are applied without knowledge of the necessary calculations. The NFPA 70E committee recognized the importance of these parameters and moved them from the endnotes to the body of the table for the 2012 edition in order to draw attention to this important information.

In contrast, the IEEE 1584 standard has been the de facto standard for calculating the arc energy levels at different points in the electrical power system. The analysis procedure begins with a complete data collection from the power system. Characteristics of the power source and the power system components, such as transformers and cables, as well as the tripping characteristics of overcurrent protective devices are identified and entered into a digital computer program. Calculations include the:

  • Bolted 3-phase short circuit current at each bus of concern in the system
  • Arc fault current at each location
  • Clearing time of the protective device protecting the bus (under arc-fault condition)
  • Working distance at each bus
  • Incident energy for each bus
  • Incident energy is the amount of energy impressed on the face and body of the electrical worker. One of the units used to measure incident energy is calories/cm2.
  • Flash protection boundary based on an incident energy of 1.2 calories/cm2

This is the generally accepted energy level that causes the onset of a second-degree burn.

It is after the above calculations have been performed that the hazard risk category and the worker’s protective clothing system for each bus under consideration are determined. 

Myth: De-energizing equipment absolves a company from having an arc flash analysis performed.

Both OSHA and NFPA have basic rules that prohibit energized work. In order to establish that a circuit is de-energized, the circuit must be approached to verify that it has been de-energized. Until the verification testing is completed, the circuit must be considered energized per NFPA 70E. Therefore, the worker who approaches the circuit for verification testing must wear full PPE.

Hiring electrical contractors to perform work does not absolve a company from assuring compliance to safe work practices. The facility owner is ultimately responsible for safety at its site and must communicate known hazards covered by NFPA 70E to the contracted worker(s). 


The continued focus on arc flash and arc blast hazards will play a critical role in reducing the frequency and severity of electrical accidents over time. Meeting the requirements of NFPA 70E will enhance workplace safety for employees and reduce the financial risk for your company. 

Reza Tajali, a registered electrical engineer in several states, is a manager of engineering for Schneider Electric Engineering Services in Nashville, Tenn. 

See articles below on electrical safety and GFCIs.

No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
A cool solution: Collaboration, chemistry leads to foundry coat product development; See the 2015 Product of the Year Finalists
Raising the standard: What's new with NFPA 70E; A global view of manufacturing; Maintenance data; Fit bearings properly
Sister act: Building on their father's legacy, a new generation moves Bales Metal Surface Solutions forward; Meet the 2015 Engineering Leaders Under 40
Cyber security cost-efficient for industrial control systems; Extracting full value from operational data; Managing cyber security risks
Drilling for Big Data: Managing the flow of information; Big data drilldown series: Challenge and opportunity; OT to IT: Creating a circle of improvement; Industry loses best workers, again
Pipeline vulnerabilities? Securing hydrocarbon transit; Predictive analytics hit the mainstream; Dirty pipelines decrease flow, production—pig your line; Ensuring pipeline physical and cyber security
Upgrading secondary control systems; Keeping enclosures conditioned; Diagnostics increase equipment uptime; Mechatronics simplifies machine design
Designing positive-energy buildings; Ensuring power quality; Complying with NFPA 110; Minimizing arc flash hazards
Building high availability into industrial computers; Of key metrics and myth busting; The truth about five common VFD myths

Annual Salary Survey

After almost a decade of uncertainty, the confidence of plant floor managers is soaring. Even with a number of challenges and while implementing new technologies, there is a renewed sense of optimism among plant managers about their business and their future.

The respondents to the 2014 Plant Engineering Salary Survey come from throughout the U.S. and serve a variety of industries, but they are uniform in their optimism about manufacturing. This year’s survey found 79% consider manufacturing a secure career. That’s up from 75% in 2013 and significantly higher than the 63% figure when Plant Engineering first started asking that question a decade ago.

Read more: 2014 Salary Survey: Confidence rises amid the challenges

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.