Commissioning, testing gensets using resistive/reactive load banks

11/12/2013


The case for reactive load bank testing

The ability to simulate varying reactive loads, which are more realistic, is the most essential benefit for a load bank that provides both kVA (resistive) and kVAR (reactive) loads. The critical differences between testing with a resistive-only load bank and a resistive/reactive load bank are compared in Table 1. A resistive-only load bank can provide adequate testing of the individual prime mover and load sharing (including load add/load shed) controls of a multiple unit facility. However, a reactive load bank allows testing of the alternator, load sharing, and transient responses because it can apply loads that approach those experienced during normal genset operation (see Table 2). 

Genset engine governors respond to loads by reducing engine speed. Figure 2 compares the transient response for a large diesel standby genset when applying a block load using restive-only and resistive/reactive load banks. The resulting initial synchronous voltage dip (Vdip1) using the 75% load at 0.80 power factor results in a voltage dip that is approximately 25% greater when compared to the equivalent resistive-only load applications. The engine speed related voltage dip (Vdip2) is similar, in both cases, due to the manufacturer’s standard V/Hz-type voltage regulator. 

During testing with a resistive-only load bank, a system that is sensitive to transient voltage dips would not necessarily provide an indication of a power supply or system condition that would lead to a potential problem during operation. Solid-state controls and power supplies are particularly sensitive to transients and can shut down unexpectedly during load changes unless specifically backed up with a dedicated power source capable of riding through the voltage and frequency transients associated with block loading of the gensets. 

Figure 2: This graph compares the transient response for a large diesel standby genset when applying a block load using restive-only and resistive/reactive load banks. Courtesy: HPS Loadbanks (Data source: Caterpillar Engine Sizer program)When testing multiple unit generator systems, the ability to share reactive loads (kVAR) equally is critical to achieving the maximum-rated power system output. When load sharing controls are not properly configured (i.e., droop settings, cross-current compensation, and measurement and control device polarities), resistive-only testing can fail to determine how the reactive load is accepted by an individual generator. In addition, the paralleling switchgear and protective relays may perform adequately under resistive load applications, but the reactive load bank testing will provide load acceptance and rejection that simulates real-world conditions more closely (see Figure 3). 

Choosing the right resistive/reactive load bank

When selecting a resistive/reactive load bank it is important to consider key features including ease of operation, onboard diagnostics, metering, the ability for an operator to control multiple units from a single controller, and data download capabilities. Load banks offering automatic step loading and duration, and data collection and reporting capabilities are beneficial in providing the necessary records to demonstrate compliance with the facility and regulatory requirements. 

Connecting load banks to a facility normally involves temporarily connecting the 3-phase power conductors to the load bus. Electrical testing and load bank rental companies can supply the necessary load banks, transformers, and cables to provide the correct service voltage for the equipment being tested. 

The proof is in the testing

Figure 3: This drawing shows the components used for a typical load test at a large facility. Courtesy: HPS LoadbanksSpecifying engineers can and should promote reactive load bank testing because it is the best way to test the entire system to identify system-wide weaknesses during commissioning and at periodic test intervals to be in compliance with the regulatory agencies. Without proof of testing, the design remains hypothetical. Testing systems with the correct size and type of resistive/reactive load bank validates the power generation system design (see Table 3). 

For existing installations, proper reactive load bank testing provides real-time data and factual evidence of reliability, functionality, and reduction of capacity resulting from aged equipment. Additionally, reactive load bank testing provides a best-case simulated real-world condition where voltage-drop, thermal heating, harmonics, and efficiency can be analyzed more effectively than with a resistive load only. 

Full system integration testing of critical systems during commissioning establishes an accurate baseline for ongoing operational performance and is a valuable tool in providing a higher level of confidence in the emergency power system.


<< First < Previous 1 2 Next > Last >>

Anonymous , 12/12/13 10:26 PM:

Great article - knowing that one can use reactive load banks to simulate aging systems to see their performance is a eye opener.
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2015 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
World-class maintenance: The three keys to success - Deploy people, process and technology; 2016 Lubrication Guide; Why hydraulic systems get hot
Your leaks start here: Take a disciplined approach with your hydraulic system; U.S. presence at Hannover Messe a rousing success
Hannover Messe 2016: Taking hold of the future - Partner Country status spotlights U.S. manufacturing; Honoring manufacturing excellence: The 2015 Product of the Year Winners
The digital oilfield: Utilizing Big Data can yield big savings; Virtualization a real solution; Tracking SIS performance
Getting to the bottom of subsea repairs: Older pipelines need more attention, and operators need a repair strategy; OTC preview; Offshore production difficult - and crucial
Digital oilfields: Integrated HMI/SCADA systems enable smarter data acquisition; Real-world impact of simulation; Electric actuator technology prospers in production fields
Improving flowmeter calibration; Selecting flowmeters for natural gas; Case study: Streamlining assembly systems using PC-based control; CLPM: Improving process efficiency, throughput
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
Warehouse winter comfort: The HTHV solution; Cooling with natural gas; Plastics industry booming

Annual Salary Survey

Before the calendar turned, 2016 already had the makings of a pivotal year for manufacturing, and for the world.

There were the big events for the year, including the United States as Partner Country at Hannover Messe in April and the 2016 International Manufacturing Technology Show in Chicago in September. There's also the matter of the U.S. presidential elections in November, which promise to shape policy in manufacturing for years to come.

But the year started with global economic turmoil, as a slowdown in Chinese manufacturing triggered a worldwide stock hiccup that sent values plummeting. The continued plunge in world oil prices has resulted in a slowdown in exploration and, by extension, the manufacture of exploration equipment.

Read more: 2015 Salary Survey

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.
This article collection contains several articles on the vital role that compressed air plays in manufacturing plants.
This article collection contains several articles on the Industrial Internet of Things (IIoT) and how it is transforming manufacturing.
This article collection contains several articles on strategic maintenance and understanding all the parts of your plant.
click me