Addenda to ASHRAE 90.1 open for comment

ASHRAE 90.1-2013, scheduled for publication later this year, has changes being proposed to strengthen its requirements.


Twenty-six proposed addenda to ANSI/ASHRAE/IES Standard 90.1-2010, Energy Standard for Buildings Except Low-Rise Residential Buildings, are open for public comment.

Twenty-two proposed addenda are open for public comment until April 21, 2013. They include:

  • Addendum bo adds requirements for use of gas condensing service water heaters in newly constructed buildings.
  • Addendum bs reduces the occupancy threshold for demand controlled ventilation from greater than 40 people per 1000 square feet, with exemptions for certain occupancies, to equal to or greater than 25 people per 1000 square feet, expanding the occupancies where demand controlled ventilation is required.
  • Addendum df replaces current minimum performance requirements for packaged Computer Room Air Conditioners shown in Table 6.8.1k with a new table based on Standard 127-2012. 
  • Addendum di prohibits use of fossil fuels and electricity for humidification above 30 percent RH and dehumidification to 60 percent RH, except in special circumstances.  Where control is required within the 30-60 percent region, a deadband is required. Where even tighter control is mandated, the system is exempted.
  • Addendum dj offers an increase in electrical/mechanical rooms in cases where the current proposed allowance of 0.42 W/sqft is not considered sufficient to provide needed vertical and horizontal illuminance given the varied configuration of electrical/mechanical rooms.  The additional allowance would have to have separate control and could not be traded off to other spaces in the building.

Three addenda under review that received public comments in earlier reviews have been revised and are open for public comment until May 6, 2013. They are:

  • Addendum ac provides for two compliance paths with regard to utilizing air spaces in conjunction with reflective surfaces.
  • Addendum bm makes the baseline building in Appendix G equivalent to 90.1-2004 for interior lighting design.
  • Addendum cl modifies IEER requirements for the air cooled air conditioners ≥65,000 Btu/hr and < 135,000 Bu/hr to increase the IEER from 12.8 to 12.9 for electric resistance heating units and 12.6 to 12.7 for gas fired units. It also revises air cooled heat pumps ≥65,000 Btu/hr and < 135,000 Bu/hr for electric resistance heating units from 12.0 to 12.2 and from 11.8 to 12.0 for gas fired units.

One addendum will close on April 28.

  • Addendum cv develops baseline energy use guidance for public assembly spaces toward assessing energy performance achievement of a proposed building. Public assembly spaces are typically designed and operated differently than surrounding spaces.

For more information on the proposed addendums and what changes they address, visit ASHRAE's public reviews page.

No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
A cool solution: Collaboration, chemistry leads to foundry coat product development; See the 2015 Product of the Year Finalists
Raising the standard: What's new with NFPA 70E; A global view of manufacturing; Maintenance data; Fit bearings properly
Sister act: Building on their father's legacy, a new generation moves Bales Metal Surface Solutions forward; Meet the 2015 Engineering Leaders Under 40
Cyber security cost-efficient for industrial control systems; Extracting full value from operational data; Managing cyber security risks
Drilling for Big Data: Managing the flow of information; Big data drilldown series: Challenge and opportunity; OT to IT: Creating a circle of improvement; Industry loses best workers, again
Pipeline vulnerabilities? Securing hydrocarbon transit; Predictive analytics hit the mainstream; Dirty pipelines decrease flow, production—pig your line; Ensuring pipeline physical and cyber security
Upgrading secondary control systems; Keeping enclosures conditioned; Diagnostics increase equipment uptime; Mechatronics simplifies machine design
Designing positive-energy buildings; Ensuring power quality; Complying with NFPA 110; Minimizing arc flash hazards
Building high availability into industrial computers; Of key metrics and myth busting; The truth about five common VFD myths

Annual Salary Survey

After almost a decade of uncertainty, the confidence of plant floor managers is soaring. Even with a number of challenges and while implementing new technologies, there is a renewed sense of optimism among plant managers about their business and their future.

The respondents to the 2014 Plant Engineering Salary Survey come from throughout the U.S. and serve a variety of industries, but they are uniform in their optimism about manufacturing. This year’s survey found 79% consider manufacturing a secure career. That’s up from 75% in 2013 and significantly higher than the 63% figure when Plant Engineering first started asking that question a decade ago.

Read more: 2014 Salary Survey: Confidence rises amid the challenges

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.