A cool way to avoid downtime

Bay Area Internet Solutions (BAIS) is one of the largest managed service providers in Northern California. After several significant service expansions in the early 2000s, the company set out to design and build its second co-location facility in Santa Clara, Calif. In designing the data center, eliminating unforeseen downtime was the main priority and the maintenance window tolerance was low.

04/01/2010


Bay Area Internet Solutions (BAIS) is one of the largest managed service providers in Northern California. After several significant service expansions in the early 2000s, the company set out to design and build its second co-location facility in Santa Clara, Calif.

In designing the data center, eliminating unforeseen downtime was the main priority and the maintenance window tolerance was low. To meet the need for high-availability services, the adjacent, 83,000-sq-ft facility with 45,000 sq ft of raised floor at full build-out needed a power infrastructure with N + 1 redundancy to consistently deliver “five nines” (99.999%) of availability. The facility also needed to be modular to accommodate future growth and technology upgrades without impacting uptime. Customer demand also dictated the need to accommodate as many as 45 servers in a single rack, which would translate to power densities upwards of 300 W/ft. Finally, to ensure the highest levels of responsiveness from its service personnel, BAIS needed to be able to monitor every piece of equipment impacting the facility's operation, from computer room air conditioning (CRAC) units to each customer's individual branch circuits.

 

The BAIS design team selected and installed six 300 kVA Liebert power protection cabinets (PPCs) with standard TP-1 transformers that provide up to 98.7% efficiency. Power is fed into the facility from the Liebert PPCs to 18 Liebert forward data channel (FDC) power distribution cabinets. To house the customers' hardware, BAIS provided rack enclosures capable of handling up to 45 high-density servers. The design team selected 47U Knurr racks from Emerson Network Power. The enclosures' perforated doors with four-point combination locks allow for up to 83% airflow, which enables the racks to be cooled without compromising the equipment's security inside.

 

BAIS' team determined that Emerson Network Power's cold aisle containment (CAC) system, with an airtight Plexiglas corridor and more than 450 CAC-optimized Knurr rack enclosures, would boost overall cooling efficiency, while simultaneously achieving rack densities of more than 10 kW. The implementation of CAC strategy enables BAIS to manage optimum temperatures at the inlet of its customers' IT equipment and allow the data center's cooling units to work in load-sharing operations.

 

To bring cool air into the contained rack rows, BAIS used the Liebert CW CRAC units with variable speed electronically commutated plug fan technology. The data center floor is surrounded by a sealed air plenum corridor, which functions as an HVAC duct between the facility's economizers and the data center's CRAC units. A fan wall comprised of more than 200 fans along the building's exterior takes in 200,000 cfm of cool air from the outside.

 

Once the data center was completed, the facility's ability to achieve efficient performance without sacrificing availability pleased both BAIS and its customers. On the cooling side, the implementation of a cold aisle containment strategy paired with a unique economizer that supplements the data center's CRAC units has enhanced the data center's hot and cold air separation.

 

Information provided by Emerson Network Power.



No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
The true cost of lubrication: Three keys to consider when evaluating oils; Plant Engineering Lubrication Guide; 11 ways to protect bearing assets; Is lubrication part of your KPIs?
Contract maintenance: 5 ways to keep things humming while keeping an eye on costs; Pneumatic systems; Energy monitoring; The sixth 'S' is safety
Transport your data: Supply chain information critical to operational excellence; High-voltage faults; Portable cooling; Safety automation isn't automatic
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Maintaining low data center PUE; Using eco mode in UPS systems; Commissioning electrical and power systems; Exploring dc power distribution alternatives
Synchronizing industrial Ethernet networks; Selecting protocol conversion gateways; Integrating HMIs with PLCs and PACs
Why manufacturers need to see energy in a different light: Current approaches to energy management yield quick savings, but leave plant managers searching for ways of improving on those early gains.

Annual Salary Survey

Participate in the 2013 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.