Providing reliable data center backup power

A Tier III data center upgrades its backup power system to provide continuous operation.

03/01/2012


Hosting.com occupies the historical Henry Ford Model-T plant in Denver (see Figure 1). The state-of-the-art Tier III data center provides co-location; hybrid, cloud, dedicated, and managed hosting; disaster recovery; and business continuance services to a global audience.

Figure 1: Hosting.com is located in the legendary Henry Ford Model-T plant in scenic Denver. Originally built in 1903, this building is where Ford made history by building the first mass-produced automobiles in the U.S. Courtesy: Generac

The data center incorporates Hosting.com’s Smart Design Standards and provides up to 10 Gb/sec of redundant connectivity for bandwidth routing optimization and more than 200 W/sq ft of power and cooling. The fully staffed network operations center uses redundant network carriers, state-of-the-art fire detection and suppression systems, redundant cooling systems, and raised flooring to help keep the equipment cool. A full security staff and sophisticated security equipment, such as cameras, keycard entrances, and biometric scanners, ensure the facility is well protected. 

To say electrical power is critical to data center operation is an understatement. Hosting.com’s Denver facility receives its power from dual redundant electrical utility feeds. The data center ensures that power is always supplied to its critical computer equipment through the use of redundant UPS systems and diesel gensets. To ensure the reliability of its backup power investment, Hosting.com fully tests the backup power system each quarter.

Hosting.com took steps to ensure that it never has to endure a power outage. Based on familiarity and experience with its products, Hosting.com selected the Gemini MPS power system from Generac. Hosting.com’s system features two Gemini units, each of which has two gensets that reside in one enclosure and operate in parallel. The system supplies up to 2 MW of electricity powered by four Volvo 16-liter 6-cylinder diesel engines.

Figure 2: The gensets, chillers, and sub-base fuel tanks are located on the facility’s roof. Courtesy: Generac

The gensets are controlled by the PowerManager digital control platform and operate within Sound Level II enclosures. The sound level at 23 ft is 73 dB. GenLink communications software allows remote computer access to all data and settings. Twin 400-gal day tanks provide fuel to the gensets and a remote 15,000-gal fuel vault provides backup.

The challenges Hosting.com faced when it upgraded its backup power system involved data center cooling, structural considerations for the cooling equipment and generators, and generator fuel storage.

Square footage in data centers is prime real estate because of the potential revenue it represents. More servers equate to more dollars for data. To provide more space for computers and servers, the backup generators and chillers were placed on the roof (see Figure 2). The electrical equipment was placed on the building’s fourth floor where the data center was located.

Figure 2: The gensets, chillers, and sub-base fuel tanks are located on the facility’s roof. Courtesy: Generac

The utility supplies 14 MW, 13.2 kV to the building via dual feeds—the only Denver location with this on-site power availability. Hosting.com does not own the facility. In order to provide power to both Hosting.com and the remaining businesses on the campus, it was necessary to split the power feed, which required upgrades to the medium-voltage switches. Discussions with the building owners and utility company representatives resulted in an upgrade plan that satisfied all parties.

The next major challenge was the fuel storage tank for the generators. The original plan was to place a tank in a fenced area in the parking lot. However, local zoning restrictions prevented it. However, using a fuel vault is allowed. The fuel storage issue was resolved to the satisfaction of zoning officials and the building owner, resulting in the installation of a 15,000-gal fuel vault with a duplex pumping system to two 400-gal sub-base day tanks.

There have been at least three power outages since the backup power system was installed in September 2009. The gensets performed flawlessly each time, coming online in less than 13 sec. Hosting.com tests the gensets with full facility-supporting load every quarter, and they have successfully passed each time.

Operating a state-of-the-art Tier III data center requires highly reliable electrical power—without interruption. Because of its reliable and cost-effective backup power system, Hosting.com should never have to endure a power outage.

Kirchner is technical support manager at Generac Power Systems.



No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2015 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
Hannover Messe 2016: Taking hold of the future - Partner Country status spotlights U.S. manufacturing; Honoring manufacturing excellence: The 2015 Product of the Year Winners
Inside IIoT: How technology, strategy can improve your operation; Dry media or web scrubber?; Six steps to design a PM program
World-class manufacturing: A recipe for success: Finding the right mix for a salad dressing line; 2015 Salary Survey: Manufacturing slump dims enthusiasm
Getting to the bottom of subsea repairs: Older pipelines need more attention, and operators need a repair strategy; OTC preview; Offshore production difficult - and crucial
Digital oilfields: Integrated HMI/SCADA systems enable smarter data acquisition; Real-world impact of simulation; Electric actuator technology prospers in production fields
Special report: U.S. natural gas; LNG transport technologies evolve to meet market demand; Understanding new methane regulations; Predictive maintenance for gas pipeline compressors
Warehouse winter comfort: The HTHV solution; Cooling with natural gas; Plastics industry booming
Managing automation upgrades, retrofits; Making technical, business sense; Ensuring network cyber security
Designing generator systems; Using online commissioning tools; Selective coordination best practices

Annual Salary Survey

Before the calendar turned, 2016 already had the makings of a pivotal year for manufacturing, and for the world.

There were the big events for the year, including the United States as Partner Country at Hannover Messe in April and the 2016 International Manufacturing Technology Show in Chicago in September. There's also the matter of the U.S. presidential elections in November, which promise to shape policy in manufacturing for years to come.

But the year started with global economic turmoil, as a slowdown in Chinese manufacturing triggered a worldwide stock hiccup that sent values plummeting. The continued plunge in world oil prices has resulted in a slowdown in exploration and, by extension, the manufacture of exploration equipment.

Read more: 2015 Salary Survey

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.
This article collection contains several articles on the vital role that compressed air plays in manufacturing plants.
This article collection contains several articles on the Industrial Internet of Things (IIoT) and how it is transforming manufacturing.
click me