Managing alarms effectively


Alarm worksheets set a good foundation

Alarm worksheets, also known as configuration sheets or pages, are used to configure the setpoints and limits for the tag names, such as a HiLimit of 110 degrees for the “Temperature” tag with a nominal setpoint of 100 degrees. By spending time to set the alarm limits and deviations correctly, fewer nuisance alarms will be generated.

Figure 3: By filling in one field in the Filters Dialog, the user can either trigger the same dialog during runtime, or change the dialog in response to operating conditions. Courtesy: Indusoft

The alarm worksheets also contain message sections that correlate to the alarm, the priority, and the selection field—all to provide the operator with more information on the alarm. For example, for a HiLimit temperature alarm, within the worksheet users can set a message (Too Hot), a priority (0-255), and a “selection” that is a user-defined field such as “Tank2.”

All the items in the alarm worksheets can be set as well as changed. Later on, we’ll see how by including values in the messages, the worksheets enable easy filtering.

Alerting operators 

The information on the alarm worksheets should appear on the screen as an alarm object. Once imported into the SCADA system, the worksheets should provide functionality to automatically e-mail alarm messages. Furthermore, the SCADA system should provide settings to control exactly when and how these alarm messages are sent. Some common settings are frequency, number of alarms, message format, response times, and escalation procedures.

Typically, the SCADA system default setting shows all active alarms, but these settings can be changed to only show certain alarms. The ability to have the “online alarm object” as the default setting, meaning it doesn’t need to pull information from a database, is vital. This is important when operators only need to view current alarms as opposed to all active alarms over a longer time period 

The SCADA system should also provide functionality to allow alarm data to be pulled from a database to get a view over a selected period of time, as this is often useful for troubleshooting by maintenance personnel and others. Characteristically, this functionality permits viewing of all alarms that have been logged. With many SCADA systems, alarms can be logged using a built-in PDF writer that turns alarms into a PDF document. This document can then be saved, e-mailed as an attachment, or printed as a report.

Using filters to manage alarms 

Filters are one of the most important features for preventing alarm overload and insufficient prioritization of alarms. Most modern SCADA systems provide easy configuration of features that offer a wide variety of sorting and filtering mechanisms.

One of the biggest alarm management issues is that operators are inundated with low-priority alarms and therefore miss critical high-priority alarms through alarm fatigue and the inability to quickly distinguish an alarm’s urgency. This is where a SCADA system with superior filtering mechanisms becomes highly valuable.

The first step in filtering was discussed in the worksheet section in which information can be prioritized to have only certain alarm limits appear. For example, the screen might display only Priority 10 and above alarms, or only the HiHiLimit alarms.

In addition to setting alarm priorities, plant personnel should consider SCADA systems that offer a filter dialog that includes an expression to let users customize the filter. For example, only HiHiLimit alarms that have the word “Hot” in the message are displayed on the screen in response to certain conditions. This expression can be hard coded, but to increase effectiveness it’s often better to create a string tag that changes values during runtime depending on specific operating conditions.

When an incident occurs, hundreds of related alarm messages can be quickly generated. Usually, only one alarm is the root cause, and the rest are symptoms of the problem. This is where many SCADA systems fail because the operators have no way to distinguish the root cause from the symptoms. But, the ability to build strings based on key criteria can help operators locate the root cause of the problem quickly.

For example, temperature alarms may start appearing with messages saying, “Tank 1 temperature too high” or “Pipe 1 pressure too low.” Operators must now quickly determine the root cause of why the temperature in Tank 1 is too high. The ability to filter all messages with a single word such as “hot,” or with a phrase like “valve closed,” can help them discover why the tank temperature is soaring. Wild card expressions can also be used to sort through words or individual phrases in the messages.

Unfortunately, many operators and even some plant managers have found managing alarms so burdensome they have almost considered them nuisances. This attitude can lead to important alarms being missed or ignored, a dangerous situation. It doesn’t have to be this way, as alarms are a key part in monitoring plant operations and can be managed effectively using off-the-shelf software tools.
One of the keys to effective alarm management is selecting the right SCADA system, one that offers advanced and easily configurable alarm management features. These features should include alarm prioritization to alert operators of conditions that require quick responses. Filtering features are also needed to enable operators to quickly locate root causes.

Implementing these and other features of modern SCADA systems as part of an effective alarm management program will improve response to alarms. This will minimize downtime, increase safety, and keep minor alarms from escalating into major incidents.

Fabio Terezinho is vice president of consulting services and product manager for InduSoft.

<< First < Previous 1 2 Next > Last >>

Khusaini , Non-US/Not Applicable, Indonesia, 08/05/13 09:12 PM:

nice article. we have the same issue in aour plant now. it will be useful
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
A cool solution: Collaboration, chemistry leads to foundry coat product development; See the 2015 Product of the Year Finalists
Raising the standard: What's new with NFPA 70E; A global view of manufacturing; Maintenance data; Fit bearings properly
Sister act: Building on their father's legacy, a new generation moves Bales Metal Surface Solutions forward; Meet the 2015 Engineering Leaders Under 40
Cyber security cost-efficient for industrial control systems; Extracting full value from operational data; Managing cyber security risks
Drilling for Big Data: Managing the flow of information; Big data drilldown series: Challenge and opportunity; OT to IT: Creating a circle of improvement; Industry loses best workers, again
Pipeline vulnerabilities? Securing hydrocarbon transit; Predictive analytics hit the mainstream; Dirty pipelines decrease flow, production—pig your line; Ensuring pipeline physical and cyber security
Upgrading secondary control systems; Keeping enclosures conditioned; Diagnostics increase equipment uptime; Mechatronics simplifies machine design
Designing positive-energy buildings; Ensuring power quality; Complying with NFPA 110; Minimizing arc flash hazards
Building high availability into industrial computers; Of key metrics and myth busting; The truth about five common VFD myths

Annual Salary Survey

After almost a decade of uncertainty, the confidence of plant floor managers is soaring. Even with a number of challenges and while implementing new technologies, there is a renewed sense of optimism among plant managers about their business and their future.

The respondents to the 2014 Plant Engineering Salary Survey come from throughout the U.S. and serve a variety of industries, but they are uniform in their optimism about manufacturing. This year’s survey found 79% consider manufacturing a secure career. That’s up from 75% in 2013 and significantly higher than the 63% figure when Plant Engineering first started asking that question a decade ago.

Read more: 2014 Salary Survey: Confidence rises amid the challenges

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.