Machine Safety: My main disconnect e-stop isn’t red with a yellow background

Does my main disconnect functioning as an e-stop need to be red with a yellow background?

07/05/2012


Jokab Safety giant E-Stop at Pack Expo 2010Does my main disconnect functioning as an e-stop need to be red with a yellow background?

 

This has long been an active area of discussion in manufacturing. In fact, using a main disconnect as an emergency device for removal of power has a long history. Some of us might remember when machines evolved to having their own machine mounted motor and or drive. Soon after this evolution the crow bar circuit emerged for emergency stopping a machine. I expect young folks today would laugh at seeing someone pick up a crow bar and throw it at the three main leads shorting out the current. An e-stop was born!

 

Banner Engineering's 30mm Mount Illuminated Emergency Stop Pushbutton is IP65-rated and is designed for emergency stop safety applications. Courtesy: Banner EngineeringFast forward to today and realize that the discussion about main disconnects being used as an e-stop device was only recently updated in NFPA 79 – 2007, Clause 10.7.4 Local Operation of the Supply Disconnecting Means to Effect Emergency Stop. The last updated NFPA 79 – 2012 made no changes to these requirements. The requirements of this Clause are: 

10.7.4.1 The supply disconnecting means shall be permitted to be locally operated to serve the function of emergency stop as follows:

Safety integration webcast, Control Engineering at www.controleng.com/webcast(1) Where it is readily accessible to the operator

(2) Where it is of the type described in 5.3.2(1), 5.3.2(2), or 5.3.2(3)

10.7.4.2 Where used as an emergency stop, the supply disconnecting means shall meet the color requirements of 10.7.3.

10.7.4.3 Disconnecting (isolating) electrical devices as described in 5.5.4, where accessible to the operator, shall also be permitted to serve the function of emergency stop. _____________________________________________________________ 

The additional requirements that I understand are that every machine needs to have at least one e-stopping device as determined by the risk assessment, that it needs to be red with a yellow background per 10.7.3 and that it needs to be accessible by the operator. ANSI B11.19 – Performance Criteria for Safeguarding normatively references NFPA 79 – 2007 as required.

Is anyone still confused?

 

Your comments or suggestion are always welcome so please let us know your thoughts. Submit your ideas, experiences, and challenges on this subject in the comments section below. Click here controleng.com/blogs if you don't see a comments box, find, and click into: Machine Safety: My main disconnect e-stop isn’t red with a yellow background, and scroll down.

 

Related reading and articles:

ANSI B11.19-2010, Performance Criteria for Safeguarding

NFPA 79 – 2012, Electrical Standard for Industrial Machinery

E-Stops and Your Compliance

E-Stops Aren’t Safety Devices

 

Contact: www.jbtitus.com for “Solutions for Machine Safety”.



No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Leaders Under 40 program features outstanding young people who are making a difference in manufacturing. View the 2013 Leaders here.
The new control room: It's got all the bells and whistles - and alarms, too; Remote maintenance; Specifying VFDs
2014 forecast issue: To serve and to manufacture - Veterans will bring skill and discipline to the plant floor if we can find a way to get them there.
2013 Top Plant: Lincoln Electric Company, Cleveland, Ohio
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Why manufacturers need to see energy in a different light: Current approaches to energy management yield quick savings, but leave plant managers searching for ways of improving on those early gains.
Electric motor power measurement and analysis: Understand the basics to drive greater efficiency; Selecting the right control chart; Linear position sensors gain acceptance
Protecting standby generators for mission critical facilities; Selecting energy-efficient transformers; Integrating power monitoring systems; Mitigating harmonics in electrical systems

Annual Salary Survey

Participate in the 2013 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.