Efficiencies, losses of liquid versus dry-type transformers

There are important tradeoffs to be made when moving transformers from outdoor locations to inside a facility.

Joe Guentert

08/21/2012


I saw a design for very large data center project a few years ago, that used twenty-four 3,000-kVA cast resin units located inside the facility, close-coupled to low voltage switchgear, in a wise "loadcenter" approach (with RC snubbers on the primary of every unit). That arrangement probably eliminated at least a million pounds of underground copper that would have been otherwise required to connect transformers to switchgear.

However, there are important tradeoffs to be made when moving transformers from outdoor locations to inside the facility. One obvious tradeoff is that indoor electrical rooms need to be enlarged to accommodate the physical space requirements of the transformers (which can be significant, especially if they include primary air switches).

Secondly, the heat from the losses of the transformers now is exhausted to inside the building, instead of simply being vented to outdoor air. In most cases, that heat will result in additional loading on the plant’s cooling system, which usually will greatly increase the magnitude of wasted energy. You have the waste heat due to losses rejected by the transformers inside the building, plus the energy consumed by the cooling system to remove that same waste heat from the building. So, efficiency becomes even more important when moving the transformers indoors.

The table below shows a comparison of four styles of transformers, with "typical" efficiencies, in the facility in the above example. Assumptions in the table are that transformers are running at average loading of 75% and that average cost of energy is $0.07 per kWH. The right column uses the Cooper FR3 Envirotemp HDC transformer as baseline, and shows the incremental cost of the other three types, using those assumptions.

Comparison of Transformer Types and Parasitic Wasted Energy

Transformer
Construction
Type

Efficiency at
75% Average
Load

Energy Wasted
Annually,
Incl. HVAC

Incremental Annual
Cost of Wasted
Energy

FR3 Liquid HDC, 55 C

99.6%

3.80 MW-Hr

$0

Cast Coil, 80 C Rise

99.2%

8.89 MW-Hr

$356,440

VPI or Cast Coil Dry, 115 C Rise

98.7%

15.32 MW-Hr

$806,384

VPI Dry, 150 C Rise

98.4%

19.62 MW-Hr

$1,203,098


Some readers will argue that there are designs of dry-type and cast coil transformers available with higher efficiencies than those typical values listed in the table. That’s true, but improving efficiency in any dry-type design almost always involves large increases in physical size and in initial cost (and often, involves large and difficult-to-manage increases in inrush current on energization).

The point is, that a liquid HDC transformer, with its average winding temperature operating at 55 C above ambient temperature, will always produce lower losses and less heat than a dry-type transformer with its windings running at an 80 C, 115 C, or 150 C temperature above ambient air temperature.



Anonymous , 03/14/13 09:27 AM:

Using the FR3 liquid filled transformer indoors in lieu of cast coil would provide the cooling savings, and reduce the copper usage mentioned in the article... best of both worlds.
The Top Plant program honors outstanding manufacturing facilities in North America. The 2012 Top Plant winners have been named.
In 2012, Plant Engineering's Product of the Year program will celebrated its 25th anniversary. Read about the 2012 winners and nominate for 2013.
The Leaders Under 40 program features outstanding young people who are making a difference in manufacturing. View the 2012 Leaders here.
Find the fake! Counterfeit electrical equipment a clear and present danger
Investment in excellence: One plant's improved productivity and quality was repaid when their company expanded the facility
Strategic uptime, Increased capacity goes right to the bottom line
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Alarm management tips, Power management, Building automation
Estimating data center PUE, Design tips for cost savings, Networked controls, NFPA 70E
Attacking Energy Costs: Strategies for showing financial return on energy management investments

2012 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

About Us | Contact Us | Advertise | Subscribe to Magazine | Site Map | Privacy Policy
Home | Channels | New Products | Media Library | Connect | Industry News | Events and Awards | Newsletters | Blogs | Magazine
Control Engineering | Plant Engineering | Consulting-Specifying Engineer
All content copyright © 2010-2013 CFE Media. All rights reserved.