Designing for safety: Simple steps for reducing electrical hazards

Incorporating simple steps into the design process is a cost-effective way to stay ahead of the curve.

12/16/2009


 

 

View the full story, including all images and figures, in our monthly digital edition
All workers have a right to a safe work environment. Indeed, the O ccupational Safety and Health Administration (OSHA) of 1970 was put in place to foster worker safety as a top priority on the job. A safer environment is a more productive environment. By providing workplaces free from serious recognized hazards, workers can concentrate on the tasks at hand.

 

MAIN DEVICES VS. SIX-HANDLE RULE

The concern with worker safety continues to increase. This has resulted in new OSHA requirements and an NFPA 70E standard on arc flash hazards. These documents cover arc flash studies, which calculate the arc flash hazard present and offer recommendations for appropriate personal protective equipment. Arc flash studies are performed to determine the level of hazards and protocol for working on energized electrical equipment, and to provide information to educate the worker on these issues. The key point to consider is the safety of those who work on energized equipment. The designer can increase worker safety by specifying equipment with features that can eliminate the need for workers to work on such equipment.

 

Article 230.71 of the National Electric Code allows the use of not more than six switches or circuit breakers (known as the six-handle rule) per service for the disconnection of power at the service entrance location. Many times services are small enough that an overcurrent protective device (OPD) of sufficient amperage is available to provide a single point disconnect for the service.

 

One advantage of a switchboard using the six-handle rule is reduced cost because a large device is not purchased. Smaller footprints are achieved in many instances because the large main device is not provided. Also, many people feel that continuity of service is better with the six-handle service boards than with a single main device. The reasoning: A fault including ground faults downstream will not have the opportunity to disconnect the entire service by causing the main OPD to trip. Generally, with a six-handle board, only the single main serving the faulted load will trip.

 

Although many services installed across the country use a six-handle service entrance switchboard, there are numerous downsides to this type of arrangement.

 

If one of the OPDs that are part of the six-service disconnects needs to be removed for service, the electrician may have to work on an energized piece of equipment. He also may be tempted to work on energized equipment if a space for one of the six disconnects was designed into the project and is being added at a later date. The electrician may consider working on the energized equipment because of the hassle involved with getting a shutdown. The only way to de-energize the equipment is through coordination with the local utility. Many times, the electrician will not want to wait for the utility to get to the site or not want to pay the utility's disconnect/reconnect fee. The electrician might decide to work on the equipment in an energized state despite the manufacturer's instructions and safety notices.

 

If the service entrance equipment is provided with a main device, the electrician is at least given a readily available option to de-energize the equipment. As an added safety feature, the main device should also be located in a separate switchboard section without load-side cables coming anywhere near line-side conductors. The main device offers additional benefits. As the facility grows, more breakers or switches can be added to the main service entrance switchboard. If all of the six disconnects were used in the initial design, the owner is faced with an expensive upgrade instead of a simple additional device (Figure 1).

 

If during the design process cost and space become a concern to the owner or the architect, the designer should adequately inform the decision makers of the possible hazards that could exist with the six-handle service equipment in lieu of a single main device. Regardless of the service entrance design chosen, the user should always be encouraged to follow the manufacturer's instructions, recommended industry safety standards, and all posted safety notices. The worker's safety should always be of the utmost concern.

 

DRAW-OUT VS. FIXED MOUNTED BREAKERS

 

This article is aimed toward electrical distribution systems that use services with overcurrent devices rated greater than 1,200 A. To enhance a worker's safety, the designer must consider designs that minimize hazardous conditions for the technician.

 

Typically, any device over 1,200 A is individually mounted vs. group-mounted or panel-mounted. Many projects use switchboards that have an individually mounted main device and possibly some feeders, which are also individually mounted and fixed (bolted on) in place.

 

Draw-out breakers are standard for low-voltage switchgear construction. Switchboards are also available with all draw-out insulated case breakers with features similar to those available in switchgear. The specifier also has the option to provide the end customer with draw-out breakers for the larger frame sizes in many switchboard models.

 

There are many advantages to draw-out construction. Ease of removal for replacement, service, or testing is the key feature. However, there are other advantages. If multiple breakers of the same frame size are present on a project, then devices can be easily moved from one location to another in case of an emergency. Inspection of the breaker for routine maintenance is simplified with draw-out breakers vs. bolted devices. Continuity of service is always desired, and a draw-out device allows the technician to safely remove the breaker for maintenance.

 

Lock-out and tag-out is a routine practice for most maintenance procedures. Most fixed-mounted breakers are provided with a device for the technician to attach his lock-out device. However, with draw-out devices, additional safeguards can be implemented with the lock-out procedure. The breaker can be withdrawn from the cubicle and locked in the disconnected position to provide a positive open circuit. The breaker can also be removed from the cubicle and the draw-out rails locked to prevent insertion of a breaker.

 

When specifying draw-out devices, the designer must take into consideration that the switchboard will typically be 5 to 10 in. deeper than the same board with fixed-mounted devices. The actual cost percentage to add the draw-out devices will vary with the size and the total number of devices within a switchboard. For a simple switchboard with a 3,000 A main, a 1,600 A feeder, a variety of smaller feeder breakers, a meter, and TVSS, the cost adder would be about 10% of the price of the switchboard. A misconception exists that all switchboards with draw-out devices must have rear access. While this is true for low-voltage switchgear and high-end Class 3 switchboards, front connections can be attained with the simplest switchboards when only a single device is in the section.

 

Another item for the specifier to consider when specifying low-voltage switchgear, which has draw-out devices as standard, is a remote racking mechanism. A remote racking mechanism is an electric motor that is attached to the breaker face and is provided with a cord connected to the control station. The operator then stands as far as 30 ft. away from, instead of directly in front of, the switchgear (Figure 2). This typically will take the technician out of the arc flash zone in front of the gear while performing a critical live bus racking operation.

 

While group-mounted molded case devices are standard for typical switchboards for amperages 1,200 A and below, individually mounted devices are available for insulated case frames for amperages of 800 A and larger. The draw-out devices provide the end user with ease of maintenance and allow a technician to perform critical maintenance operations and a positive circuit disconnect that is not available with a fixed, bolted-in device. Additional safety features such as remote racking can also be specified when switchgear designs are implemented.

 

Providing a safe and secure work environment is a must for any company wishing to compete in this global economy. Incorporating simple steps into the design process is a cost-effective way to stay ahead of the curve.

 

 

Author Information

Schlobohm has been a senior specification engineer at GE Consumer & Industrial in Houston since 1993. He provides layout assistance, equipment selection, and application and technical support for power distribution and control equipment to central and south Texas consulting engineers. Schlobohm holds a BSEE from Texas A&M University and has been a licensed professional engineer in the state of Texas since 1992.

 



No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Leaders Under 40 program features outstanding young people who are making a difference in manufacturing. View the 2013 Leaders here.
The new control room: It's got all the bells and whistles - and alarms, too; Remote maintenance; Specifying VFDs
2014 forecast issue: To serve and to manufacture - Veterans will bring skill and discipline to the plant floor if we can find a way to get them there.
2013 Top Plant: Lincoln Electric Company, Cleveland, Ohio
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Bring focus to PLC programming: 5 things to avoid in putting your system together; Managing the DCS upgrade; PLM upgrade: a step-by-step approach
Balancing the bagging triangle; PID tuning improves process efficiency; Standardizing control room HMIs
Commissioning electrical systems in mission critical facilities; Anticipating the Smart Grid; Mitigating arc flash hazards in medium-voltage switchgear; Comparing generator sizing software

Annual Salary Survey

Participate in the 2013 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.