Decoding "efficiency" for mechanical draft fans

05/17/2013


Efficiency ranges

The efficiency and power requirements of a draft fan depend on the type and style of the blades used in a particular application (See Figure 2). These two variables have an opposite relationship to each other. For example, a fan with a low horsepower demand will have a high calculated efficiency.

Figure 2: Centrifugal fan characteristics curve. Courtesy: ProcessBarron

Classically, fan blade designs are categorized in three major groups with relative efficiencies and degrees of power:

Radial: 

  • Straight radial blade (RB) – lowest efficiency (65% to 72%) and therefore highest horsepower demand
  • Radial tip (RT) – low efficiency (72% to 78%) and therefore high horsepower demand

Forward curved (FC) -  lower efficiency (72% to 76%) and therefore higher horsepower demand

Backward inclined (BI)

  • Single thickness backward inclined flat (BF) - high efficiency (79% to 81%) and therefore low horsepower demand
  • Single thickness backward curved (BC) – higher efficiency (80% to 82%) and therefore lower horsepower demand
  • Dual thickness airfoil (AF) – highest efficiency (83% to 88%) and therefore lowest horsepower demand 

Efficiency variations

A mechanical draft fan’s efficiency is dependent on the system pressure used in each calculation. System pressure requirements can take many different forms, leading to an array of ratings. The primary variations are defined below:

  • Static pressure rise: Static pressure differential between the fan outlet and inlet: SPR = SP2 – SP1 (SPR = Static pressure rise; SP1 = SP2 = Static pressure at fan inlet and outlet)
  • Fan total pressure: Total pressure differential between the fan outlet and inlet: FTP = TP2 – TP1 (FTP = Fan total pressure; TP1 = TP1 = Total pressure at fan inlet and outlet)
  • Fan static pressure: This represents the pressure difference between the fan total pressure and the velocity pressure at the fan outlet: FSP = FTP – VP2 (FSP = Fan static pressure; VP2 = Fan outlet velocity pressure)

There are corresponding efficiencies associated with each of these pressures:

  • Static efficiency (ȠSPR) is calculated utilizing static pressure rise. The relative comparison with other efficiencies can be mathematically expressed in the following form: ȠSSPR < Ƞt
  • Fan total efficiency (Ƞt) is calculated utilizing fan total pressure and bears the following relationship to static efficiency and fan static efficiency:  Ƞt > ȠSPR> ȠS
  • Fan static efficiency (ȠS) is calculated utilizing fan static pressure: ȠS < ȠSPR < Ƞt 

The Air Movement and Control Association (AMCA), an association of air system equipment manufacturers, provides rating guidelines to ensure a common platform for the engineers, manufacturers, and users. However, each project is unique and ultimate project execution goals are subject to the interpretation of the players involved. 

Evase effects

When calculating efficiency, static pressure regain due to an evase at the fan outlet may also be accounted for.

Evase output = Static pressure + (VP1 – VP2) x Conversion efficiency

Conversion efficiency may range from 60% to 80%. This has a dramatic effect on calculated efficiency and power input for some mechanical fan applications. Evase effectively reduces a fan’s working pressure requirements and thus reduces input power to the fan shaft. In order to avoid any confusion and to support fair comparisons, project specifications need to be abundantly clear if evase is to be considered when evaluating fans for efficiency. 

Conclusion

Understanding the concepts of power and efficiency and their appropriate use in evaluation of the mechanical draft fans will undoubtedly help plants and engineers to clearly define the requirements and in return they will receive better response from the manufacturers. Evaluation of mechanical draft fans based on “efficiency” may not offer the desired benefit to the clients.

As discussed in this article, an apparent higher efficiency does not necessarily mean a lower input power to the fan. The clients are the rate payers and they pay for the actual power used to drive the fans. So, for relative comparisons, “input power to the fan” should be evaluated rather than the calculated efficiency. 

Nurul “Moni” Talukder, PE, is a chief engineer in the Air Handling Group at ProcessBarron in Pelham, Ala. ProcessBarron is a leader in the design, manufacturing, installation, and maintenance of air and material handling equipment for heavy industry. Moni can be reached at: mtalukder(at)processbarron.com.


<< First < Previous 1 2 Next > Last >>

No comments
The Top Plant program honors outstanding manufacturing facilities in North America. View the 2013 Top Plant.
The Product of the Year program recognizes products newly released in the manufacturing industries.
The Engineering Leaders Under 40 program identifies and gives recognition to young engineers who...
The true cost of lubrication: Three keys to consider when evaluating oils; Plant Engineering Lubrication Guide; 11 ways to protect bearing assets; Is lubrication part of your KPIs?
Contract maintenance: 5 ways to keep things humming while keeping an eye on costs; Pneumatic systems; Energy monitoring; The sixth 'S' is safety
Transport your data: Supply chain information critical to operational excellence; High-voltage faults; Portable cooling; Safety automation isn't automatic
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Plant Engineering case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Maintaining low data center PUE; Using eco mode in UPS systems; Commissioning electrical and power systems; Exploring dc power distribution alternatives
Synchronizing industrial Ethernet networks; Selecting protocol conversion gateways; Integrating HMIs with PLCs and PACs
Why manufacturers need to see energy in a different light: Current approaches to energy management yield quick savings, but leave plant managers searching for ways of improving on those early gains.

Annual Salary Survey

Participate in the 2013 Salary Survey

In a year when manufacturing continued to lead the economic rebound, it makes sense that plant manager bonuses rebounded. Plant Engineering’s annual Salary Survey shows both wages and bonuses rose in 2012 after a retreat the year before.

Average salary across all job titles for plant floor management rose 3.5% to $95,446, and bonus compensation jumped to $15,162, a 4.2% increase from the 2010 level and double the 2011 total, which showed a sharp drop in bonus.

2012 Salary Survey Analysis

2012 Salary Survey Results

Maintenance and reliability tips and best practices from the maintenance and reliability coaches at Allied Reliability Group.
The One Voice for Manufacturing blog reports on federal public policy issues impacting the manufacturing sector. One Voice is a joint effort by the National Tooling and Machining...
The Society for Maintenance and Reliability Professionals an organization devoted...
Join this ongoing discussion of machine guarding topics, including solutions assessments, regulatory compliance, gap analysis...
IMS Research, recently acquired by IHS Inc., is a leading independent supplier of market research and consultancy to the global electronics industry.
Maintenance is not optional in manufacturing. It’s a profit center, driving productivity and uptime while reducing overall repair costs.
The Lachance on CMMS blog is about current maintenance topics. Blogger Paul Lachance is president and chief technology officer for Smartware Group.