Handheld temperature measurement devices

Joseph L. Foszcz, PE/CPE, Senior Editor, Plant Engineering Magazine -- Plant Engineering, 9/1/2001

  • Types
  • Applications
Sections:
Contact devices
Noncontact Devices

Temperature measurements are fundamentally important to many industrial processes. Many measurements are made with a probe in or on a pipe or vessel. However, if an object cannot be contacted, measuring temperature may be difficult. Contact sensors such as thermometers, thermocouples, and RTD's are accurate and cost effective but not always practical. For many industrial applications, optical and infrared temperature sensors can carry out measurements virtually impossible for contact sensors.

Contact devices

There are several popular methods for measuring temperature by contact. Readings are produced by the expansion of a liquid or metal, the generation of a current in the presence of heat, or the generation of resistance to current flow in the presence of heat. The first two are called active devices; they generate a signal. The third is called a passive device; it creates a blockage. All these devices react proportionally to the temperature they contact.

Liquid-in-glass thermometers

Liquid-in-glass thermometers consist of a glass envelope, a responsive liquid, and an indicating scale. They were invented about 300 yr ago and are still the most commonly used temperature-indicating devices.

Some advantages of these thermometers are:

  • Low cost
  • Simple to use
  • Ease of checking for damage
  • No power requirement.

Bimetal thermometers

Bimetal thermometers use a composite material made up of strips of two or more metals joined together that have different expansion rates. The strip tends to change its curvature when subjected to a change in temperature.

These devices will retain their accuracy indefinitely. Accuracy is within 1% of scale range at any point on the scale. They can be used beyond their range by 100% below 250 F, 50% up to 500 F, and 10% up to 750 F without damage.

Thermocouples

When dissimilar metal wires are joined and the joint is heated, a voltage is produced that is proportional to the temperature. Various combinations of metal wires respond differently to temperatures.

The selection of thermocouple wire depends on a variety of factors including:

  • Temperature to be measured
  • Compatibility with the ambient atmosphere
  • Cost
  • Millivolt output
  • Linearity.

RTDs

Resistance temperature detectors (RTDs) are based on the change of electrical conductivity with temperature. They consist of an encapsulated coil of wire (the sensing element), internal lead wires, supporting and insulating material, and a protective case. Platinum wire has the optimum characteristics for service over a wide temperature range.

Noncontact Devices

When temperatures are extremely high or the object to be measured is remotely located, noncontact devices must be used. These devices use the radiant energy from the hot source to determine its temperature.

Optical pyrometers

Optical pyrometers measure the intensity of the radiant flux emitted in a narrow wavelength interval in the visible spectrum. The temperature of the target is determined from its spectral radiant intensity. Temperatures from 1400 to 5200 F can be measured. With special absorbing screens, this can be extended to 10,000 F.

Infrared sensors

Infrared sensors collect radiation from a target. The infrared energy is isolated and measured using photosensitive detectors. The detectors convert the infrared energy to an electrical signal, which is then converted into a temperature value. For accurate temperature readings, the target should be larger than the instrument's field of view. This device can measure temperatures from -32 to 5000 F.

Temperature sensors

Contact Noncontact
Liquid-in-glassOptical
BimetallicInfrared
Thermocouple
RTD

Liquid-in-glass Thermometers
Liquid Temperature range, F
Mercury-38 to +1110
Mercury alloys-76 to +250
Organic alloys-328 to +450

Thermocouple comparison
ISA Type Positive wire Negative wire Recommended temperature, F Acceptable ambient conditions
TCopperConstantan -450 to +750Oxidizing reducing
JIronConstantan0 to +1650Reducing
KChromelAlumel0 to +2300Oxidizing or neutral
EChromelConstantan-300 to +1600Oxidizing
R,SPlatinum-rhodiumPlatinum0 to +2800Oxidizing
BPlatinum 70-Rh30Platinum 94-Rh60 to +3200Inert or slow oxidizing

Email
Print
Reprint
Learn RSS

Talkback

We would love your feedback!

Post a comment

» VIEW ALL TALKBACK THREADS

Related Content

Related Content

 

By This Author

Sponsored Links



 
Advertisement
SPONSORED LINKS

More Content

  • Blogs
  • Podcasts
  • Photos

Blogs


Sorry, no blogs are active for this topic.

» VIEW ALL BLOGS RSS

Photos

  • 2007 Product of the Year Winners
    This year's Plant Engineering Product of the Year winners were honored at the Manufacturing Summit in Chicago.
  • Top Plant: GEMA
    The game plan for GEMA (Global Engine Manufacturing Alliance) focuses on best-in-class execution
  • Top Plant: SEW Eurodrive
    SEW Eurodrive builds a culture based on employee empowerment and continuous improvement.
Advertisements





NEWSLETTERS
Click on a title below to learn more.

Plant Engineering PlantMail!
Plant Engineering Hotwire
Plant Engineering Hotwire Automation
Plant Engineering Maintenance Connection
Plant Engineering Sustainable Manufacturing
©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites